georgia-market.com moderated newsgroup and market bazzar   >   Dalton   >   Electronics   >   Honeywell fan and limit control 11.5" L4064W1106 hvac

Honeywell fan and limit control 11.5" L4064W1106 hvac


Provides fan operation control and high limit protection on all types of forced air heating systems. Used in line voltage, low voltage or powerpile applications. Electrical ratings: Fan - 14 amps @ 120v, 7 amps @ 240v. Limit - 8 amps @ 120v, 4 amps @ 240v. L4064A - Economy O.E.M. type. Helical bimetal sensing element; no metal cover. L4064B - Standard replacement type. Helical bimetal sensing element; manual/automatic fan switch, metal cover. L4064D - Spiral sensing element for shallow insertion. Manual/automatic fan switch, metal cover. L4064W - Helical bimetal sensing element and bimetal heater switch which delays fan operation for 20 to 90 seconds after call for heat. Used in most high-efficiency furnaces and other applications to eliminate cold draft problems upon system startup. Manual/automatic fan switch, metal cover.
Honeywell L4064W1106 Fan and Limit Controller with 125 F fan on and 100 F fan off stops, 200 F high limit stop and 11 1/2 in. in
Honeywell L4064W1106 Fan and Limit Controller with 125 F fan on and 100 F fan off stops, 200 F high limit stop and 11 1/2 in. in
Fan and Limit Controller with 125 F fan on and 100 F fan off stops, 200 F high limit stop and 11 1/2 in. insertion
Three wiring terminal options available for easy installation: • Push-in receptacles for stripped wire. • Female receptacles for 1/4 in. male flag connectors. • Field add-on screw terminals. • Controls adapt to many competitive mounting holes in replacement applications. • Available in a variety of fan and high limit setting ranges. • L4064B,W models have manual fan switch that overrides fan control to keep fan running continuously. • SUPER TRADELINE models include deluxe case with mounting adapters for easy installation and strain relief bushings to protect wiring from field abuse.
Description Fan and Limit Controller with 125 F fan on and 100 F fan off stops, 200 F high limit stop and 11 1/2 in. insertion
Application Forced warm air heating systems
High Limit Temperature Range (F) 100 F to 250 F
High Limit Temperature Range (C) 38 C to 121 C
Element Insertion Length (in.) 11 1/2 in.
Element Insertion Length (mm) 292 mm
Fan-on Range (F) 20 to 90 sec. after call for heat
Fan-on Range (C) 20 to 90 sec. after call for heat
Fan-off Range (F) 50 F to 200 F
Fan-off Range (C) 10 C to 93 C
Switching Action Fan switch makes and high limit switch breaks on temperature rise.
Timing 20 to 90 sec. after call for heat
Electrical Rating Fan (AFL) 14 A @ 120 Vac
Electrical Rating Fan (AFL) 7 A @ 240 Vac
Electrical Rating Fan (ALR) 84 A @ 120 Vac
Electrical Rating Fan (ALR) 42 A @ 240 Vac
Electrical Rating Limit (AFL) 4 A @ 240 Vac
Electrical Rating Limit (AFL) 8 A @ 120 Vac
Electrical Rating Limit (ALR) 24 A @ 240 Vac
Electrical Rating Limit (ALR) 48 A @ 120 Vac
Pilot Duty Ratings 2 A @ 24 Vac
Pilot Duty Ratings 0.25 A @ 0.25 to 12 Vdc
Operating Temperature Range (F) 50 F to 115 F
Operating Temperature Range (C) 10 C to 46 C
Differential Temperature (F) High limit 25 F
Differential Temperature (C) High limit 14 C
Maximum Ambient Temperature (F) Switch: 115 F; Sensing Element: 350 F
Maximum Ambient Temperature (C) Switch: 46 C; Sensing Element: 177 C
Mounting Surface mounting or bracket (rigid or swivel)
Dimensions (in.) 4 9/32 in. high x 3 in. wide x 1 19/32 in. deep excluding element
Dimensions (mm) 109 mm high x 76 mm wide x 40 mm deep excluding element
Approvals, Underwriters Laboratories Inc Listed File MP466, Guide MBPR
Approvals, Canadian Standards Association Certified: File No. LR1622
Comments Turns fan on and off according to plenum temperature. With helical bimetal sensing element. High limit stop set at 200F (93 C). Jumper in. With timed on fan feature and manual fan switch. Replaces L4064T, Y.